[What measures should we take when the freezer encounters a high-pressure alarm?]
Release date:[2020/1/2] Is reading[725]次

Jincheng freezer manufacturer's warm reminder: During the use of the freezer, some problems will inevitably be encountered, but don't panic when encountering problems, and rationally find the reason to solve the problem in time. Today, I will explain to you what measures we should take when the freezer encounters a high-pressure alarm.


Generally, the refrigerator is equipped with a full set of protection devices. When a high-voltage alarm occurs on the refrigerator, it will automatically start the protection device, and the corresponding fault indicator will be on. At this time, the refrigeration unit will not run and the operator will need to communicate. Check the following methods, or contact the refrigerator manufacturer for instructions.


1. If the water-cooled freezer has a high-pressure alarm, it is mainly related to the cooling water system. The water-cooled freezer provides circulating cooling water through the cooling water tower. If you forget to open the cooling water valve when you use it, the cooling water cannot be used. Circulating supply to the chiller will cause high-pressure failure. In addition, check whether the cooling water tower is faulty and can not safely and stably transport the cooling water;


2. The cooling water flow is too small, or the temperature is too high, and the heat dissipation is not good, this problem will also occur. The cooling water flow is small. Check whether the size of the supporting pipelines matches the size of the refrigeration unit or whether the water valve is opened to an oversized position. If it is an air-cooled refrigerator, we need to check whether the ambient temperature of the installation exceeds 40 ° C. If so, the heat must be removed in a timely manner to ensure that the refrigeration unit is in an environment with air circulation;


3. If the refrigerating unit is used for a long time, it is easy to cause scale and other debris to accumulate in the tube wall or the condenser copper tube. This will inevitably affect the refrigeration cycle system. Therefore, we regularly perform maintenance and cleaning for the refrigerating machine according to the maintenance time recommended by the manufacturer. Work (cleaning cooling water systems, cleaning condensers, replacing filters, etc.);


4. Check whether the refrigerant is excessive. The refrigeration unit will be filled with an appropriate amount of refrigerant before leaving the factory. Therefore, if there is no refrigerant leakage, the user does not need to charge the refrigerant. Too much refrigerant will only affect the unit's normal use.


5. Is the expansion valve opening too small? This one point, we can slowly adjust the opening degree of the expansion valve to eliminate the fault.


Jiangsu Jincheng Air Conditioning Engineering Co., Ltd. focuses on:

Industrial air-conditioning, chemical fiber industrial air-conditioning, chemical fiber industrial refrigeration, textile industrial air-conditioning, clean room refrigeration, ventilation ducts, cooling towers, freezers and other air-conditioning units and accessories.


Jincheng can bring high-quality industrial air-conditioning products and satisfactory services to everyone.


You also want to know more product information, please contact: Mr. Song 13705113637 Website: http://m.pc20080808.cn/


Keyword:
ADD:No. 18, Rongguang Road, National High-tech Park, Yancheng City, Jiangsu Province Phone: 0086-13705113637 Tell: 0086-0515-88809180 Fax: 0086-0515-88809181 E-Mail: jsjckt@126.com
Copyright ? 2018 All rights reserved
Copyright Jiangsu Jin Cheng Air Conditioning Engineering Co.,Ltd 技術支持:中國丙綸網